Drager Short-Term Detection Tubes - Ammonia 5/b (Pack of 10)

PRODUCT CODE:
8101941

These tubes are designed for spot-measurements and must be used with the Drager Accuro Gas Detection Pump. Buy now from Frontline Safety.

£90.05 inc VAT
£75.04
Loading...

Product description

Drager Detection Tubes - Ammonia 5/b (Pack of 10)

These Ammonia short-term detection tubes have a shelf life of 2 years and additionally may be able to detect 1,1-Dimethylhydrazine.

One pack contains 10 tubes.

The Accuro Gas Detection Pump from Draeger Safety is required to use short-term gas detection tubes.  View more information on this product by clicking here .

Key Features

  • Reach difficult measurement areas with the tubes, pump and accessories
  • Carry out measurements on the spot
  • Measurement results may take between 10 seconds and 15 minutes depending on the type of tube used
  • Applications for use include variations in concentrations in the workplace, contamination of breathing zones, pre-entry checks and confined space entry
Specification
Application Range  
Standard Measuring Range: 5 to 100 ppm
Number of Strokes n: 1
Time for Measurement: approx. 10 s
Standard Deviation: ± 10 to 15 %
Color Change: yellow --> blue
   
Ambient Operating Conditions  
Temperature: 10 to 50 °C
Absolute Humidity: < 20 mg H2O / L
   
Reaction Principle  
NH3 + pH-indicator --> blue reaction product
 
Cross Sensitivity
Other basic substances such as e.g. organic amines are indicated as well.
The indication is not affected by:
300 ppm nitrous fumes
2,000 ppm sulfur dioxide
2,000 ppm hydrogen sulfide
 
Extension of the Measuring Range
Using n= 2 strokes, divide the reading by 2; the measuring range will be 2.5 to 50 ppm.
Reviews