Drager Detection Tubes - Ethylene 0.1/a (Pack of 5)

PRODUCT CODE:
702796-01

These tubes are designed for spot-measurements and must be used with the Drager Accuro Gas Detection Pump. Buy now from Frontline Safety.

Loading...
£81.48
Final product price inc VAT

Product description

Drager Detection Tubes - Ethylene 0.1/a (Pack of 5)

Worldwide, the Dräger short-term detector tubes have proven to be a very cost-effective and reliable way for the measurement of gas. Ethylene 0.1/a (5) (Measurement range: 0.1 to 5 ppm).

Note: This product has a shelf life of 2 years and comes in a pack of 5 tubes.

Specification
Application Range  
Standard Measuring Range: 0.2 to 5 ppm
Number of Strokes n: 20
Time for Measurement: approx. 30 min
Standard Deviation: ± 15 to 30 %
Color Change: pale yellow --> greyish blue
   
Ambient Operating Conditions  
Temperature: 10 to 40 °C
Absolute Humidity: 5 to 20 mg H2O / L
   
Reaction Principle  
CH2=CH2 + Pd-Molybdate complex --> blue reaction product
 
Cross Sensitivity
Other similar compounds are indicated in addition to ethylene, e.g.:
100 ppm butadiene result in a reading of 1 ppm
50 ppm butylene result in a reading of 1 ppm
5 ppm propylene result in a reading of 1 ppm
20 ppm hydrogen sulfide result in a reading of 2 ppm
25 ppm CO change the indicating layer to a greyish blue.