Drager Short Term Detection Tubes - Phosphine 0.1/b in Acetylene (Pk of 10)

PRODUCT CODE:
8103341

These tubes are designed for spot-measurements and must be used with the Drager Accuro Gas Detection Pump. Buy now from Frontline Safety.

£116.96 inc VAT
£97.47
Loading...

Product description

Drager Short Term Detection Tubes - Phosphine 0.1/b in Acetylene (Pk of 10)

These Drager Safety short-term detection tubes are for phosphine gas in acetylene.  They have a measurement range of 0.1 to 15 ppm and have a shelf life of 2 years.

Please note that one pack contains 10 tubes.

The Accuro Gas Detection Pump from Draeger Safety is required to use short-term gas detection tubes.  View more information on this product by clicking here

Key Features

  • Obtain readings from hard to reach places with the tubes, pump and accessories
  • Carry out measurements on the spot
  • 10 seconds to 15 minutes is the potential time frame for readings to be taken and is dependent on the type of tube used
  • Pre-entry checks and confined space entry are two applications which can use tubes
  • Additional applications may include variations in concentration levels and also contamination of breathing areas 
Specification
Application Range  
Standard Measuring Range: 0.1 to 1 ppm / 1 to 15 ppm
Number of Strokes n: 10 / 1
Time for Measurement: approx. 4 min / approx. 20 s
Standard Deviation:  ± 15 to 20 %
Color Change: yellow orange --> red violet
   
Ambient Operating Conditions  
Temperature: 2 to 40 °C
Absolute Humidity: < 20 mg / L
   
Reaction Principle  
PH3 + HgCI2 --> Hg-phosphide + HCI
HCI + pH-indicator --> red violet reaction product
 
Cross Sensitivity
Arsin and hydrogen sulfide will be indicated with differing sensitivities.
Reviews