TSI Q-Track IAQ Monitor with Model 982 Probe and Datalogging
The Q-Track Monitor (model 7575) from TSI is an indoor air quality monitor. This particular monitor comes with a model 982 IAQ probe for CO, CO2, temperature and humidity monitoring.
As standard the Q-Trak Indoor Air Quality Monitor will display up to five measurements simultaneously. It has a datalogging capability and the ability to download statistics and data for analysis and reporting. TrakPro software is required for this, which is provided with the instrument.
The Q-Trak IAQ monitor is provided alongside a hard-carrying case, USB cable for download, universal power supply, four alkaline batteries, a manual and a calibration certificate.
- Handheld monitor
- Lightweight and easy to carry
- Compatible with a range of other plug-in probes
- Suitable for various applications – IAQ investigations, industrial hygiene surveys, baseline trending and screening, building commissioning, tracking down emissions to their source (point source location)
Monitor Dimensions |
9.7 x 21.1 x 5.3 cm (3.8 x 8.3 x 2.1”) |
Probe Dimensions |
17.8 x 1.9cm (LxD) / 7.0 x 0.75” |
Weight (with batteries) |
0.36 kg (0.8lbs) |
Power Requirements |
4 x AA alkaline batteries (or AC adapter, both are included) |
Log Intervals / Capabilities |
1 second up to 1 hour (user selectable) |
Time Constants |
1 sec, 5 sec, 10 sec, 20 sec, 30 sec (user selectable) |
Temperatures |
Operating Temperature - 5 to 45°C (40 to 113°F) |
Barometric Pressure |
Range - 517.15 to 930.87 mm Hg (20.36 to 36.648 in. Hg) Accuracy - ±2% of reading |
% Outside Air |
Range - 0 to 100% Resolution - 0.1% |
Probe Sensor Type |
Carbon Monoxide (CO) – Electro-chemical |
Probe Range |
Carbon Monoxide (CO) – 0 to 500ppm |
Probe Accuracy |
Carbon Monoxide (CO)5 – ±3% of reading or 3 ppm, whichever is greater |
Probe Resolution |
Carbon Monoxide (CO) – 0.1 ppm |
Probe Response Time |
Carbon Monoxide (CO) – <60 seconds to 90% step change |
|
3 Accuracy with instrument case at 25°C (77°F), add uncertainty of 0.03°C/°C (0.05°F/°F) for change in 4 Accuracy with probe at 25°C (77°F). Add uncertainty of 0.2% RH/°C (0.1% RH/°F) for change in probe 5 At 25°C (77°F). Add uncertainty of 0.36%/°C (±0.2%/°F) for change in temperature. 6 At calibration temperature. Add uncertainty of 0.5%/°C (±0.28%/°F) for change in temperature |