Sensepoint XRL Bluetooth Charcoal with Modbus
The Sensepoint XRL Bluetooth Charcoal (with Modbus) embodies an award-winning design with an aluminium housing. This system is a fixed-point gas leak detector that is easy to install, operate and maintain. The addition of the modbus provides the Sensepoint XRL with greater functionality and the system is designed to meet the requirements of industrial applications. Maintenance and control are easy to undertake as the system allows you to check its detection history, the ability to read gas concentrations in real time and reconfigure the system’s settings.
Applications in which this device may be used in includes fuelling depots, petrochemical plants, vehicle test facilities, battery charging facilities, water treatment plants and manufacturing facilities and factories. There are different variations of this system available and more information can be found below.
There are different sensor types to choose from including flammable, oxygen or toxic. The device is IP66 protected making the system dust and water-resistant, giving you peace of mind. In terms of output this configuration of the Sensepoint XRL supports modbus RTU. Using the modbus allows the Sensepoint XRL to communicate between other devices making it ideal to integrate the device into your systems.
The addition of Bluetooth connectivity allows the Sensepoint XRL to connect to a smartphone for wireless maintenance and configuration via the dedicated mobile app. The combination of the app and the Sensepoint device allows reporting to be automated thereby increasing your efficiency and cutting down administration time. Diagnostic data is simple to gain access to and system forms calibration reports.
There are a range of accessories available such as the calibration cap, flow housing, collecting cone, weather protection, pole mount bracket kit and duct mount kit. If you would like more information, then please get in touch with us.
Available options include;
Part Number |
Description |
SPLIO1BMXCMAZZ |
XRL, Modbus, O2 0 to 25% vol, ATEX/IECEx, NEMA 4X, IP66, 2 x M20, Charcoal, BLE Enabled |
SPLIC1BMXCMAZZ |
XRL, Modbus, CO 300ppm (adjustable 50 & 1000 ppm) ATEX/IECEx, NEMA 4X, IP66, 2 x M20, Charcoal, BLE Enabled |
SPLIH1BMXCMAZZ |
XRL, Modbus, H2S 50ppm (adjustable 10 & 50 ppm) ATEX/IECEx, NEMA 4X, IP66, 2 x M20, Charcoal, BLE Enabled |
SPLIH2BMXCMAZZ |
XRL, Modbus, H2S 100 ppm (adjustable 50 & 200 ppm) ATEX/IECEx, NEMA 4X, IP66, 2 x M20, Charcoal, BLE Enabled |
SPLIG1BMXCMAZZ |
XRL, Modbus, H2 1000 ppm , ATEX/IECEx, NEMA 4X, IP66, 2 x M20, Charcoal, BLE Enabled |
SPLIN1BMXCMAZZ |
XRL, Modbus, NO2 20 ppm , ATEX/IECEx, NEMA 4X, IP66, 2 x M20, Charcoal, BLE Enabled |
SPLIF6BMXCMAZZ |
XRL, Modbus, Catlaytic 100% LEL( adjustable between 20 & 100% LEL) , ATEX/IECEx, NEMA 4X, IP66, 2 x M20, Charcoal, BLE Enabled |
- Charcoal grey colour
- Easy to use – can save training time
- User friendly as the system uses multi-colour indicator showing users the status of the system and knowing what detectors need urgent attention or are warning the user of danger
- The system can be calibrated by one person
- IP66 rated
- The system can be managed without the need for a physical connection
- Comes with a Modbus
- Sink or source mode
Dimensions |
118 x 159 x 93 mm ( 4.4 x 6.2 x 3.6 in ) |
Weight |
1400 g (3.1 lb) |
Casing Material |
Aluminum alloy LM20 (charcoal) |
Ingress Protection Rating |
IP66, NEMA 4X |
Lifetime |
10 years (excludes sensor) |
Available sensors flammable, toxic gases and oxygen ranges |
|
Power Supply DC Input Voltage |
24 V DC† |
AC Input Voltage |
24 V AC‡, 50/60 Hz |
Inrush Current |
850 mA |
Analog Output |
0 to 22 mA |
Digital Output |
Modbus RTU |
Maximum Power Consumption mA Versions |
< 1.5 W (toxic), < 2.6 W (flammable) |
Modbus Versions |
< 1.0 W (toxic), < 2.0 W (flammable) |
Connection Type |
Pluggable rising clamp style
|
User Interface Visual Indicator |
|
Wireless Interface |
Bluetooth 4.0 (Bluetooth Low Energy). Dedicated mobile app, enabling wireless configuration and maintenance. Connect up to 10 m (30 ft) away (mobile device dependent). Use a compatible smartphone or other mobile device running Android 4.3 or above. |
Operating Temperature |
−40 to 65 °C (−40 to 140 °F) |
Storage Temperature |
0 to 30 °C (32 to 86 °F) |
Humidity |
0 to 99% (non-condensing) |
Atmospheric Pressure |
90 to 110 kPa |
Certifications Electrical Safety |
EN/IEC/UL 61010-1 CSA C22.2 No. 61010-1-12 |
EMC |
EN 50270:2015 |
Radio |
RED, FCC, IC |
Hazardous Area |
|
Gas Performance |
CSA C22.2 No.152-M1984, UL 2075, AS 1668.2 |
- † mA versions: 11 to 32 VDC, Modbus versions: 9 to 32 VDC
- ‡ All versions: 20 to 27 VAC
- § LED behavior in normal condition can be changed by the user: green confidence flash, solid green or off